Relay-Version: version B 2.10 5/3/83; site utzoo.UUCP Posting-Version: version B 2.10.1 6/24/83; site decwrl.UUCP Path: utzoo!watmath!clyde!burl!mgnetp!ihnp4!zehntel!dual!decwrl!johnsson From: johnsson@decwrl.UUCP (Richard Johnsson) Newsgroups: net.lan Subject: Re: inter-building ethernet grounding Message-ID: <3430@decwrl.UUCP> Date: Fri, 24-Aug-84 12:38:21 EDT Article-I.D.: decwrl.3430 Posted: Fri Aug 24 12:38:21 1984 Date-Received: Wed, 29-Aug-84 01:24:45 EDT References: <433@cornell.UUCP> Organization: DEC Western Software Lab, Los Altos, CA Lines: 17 The Xerox Palo Alto complex of buildings had a lightning induced Ethernet failure several years (which probably led to the emphasis on grounding in the Blue Book). Basically the cable became grounded in two buildings about 500 feet apart by cable taps accidentally touching metal cable trays. A nearby lightning strike induced a large, temporary potential difference between the buildings and fried several tranceivers. Unfortunately about six of the tranceivers died shorted rather than open and we had a lot of fun learning how to use a TDR to find them. Richard Johnsson DEC Western Software Lab, Los Altos, CA (415) 949-1494 {decvax,ucbvax,ihnp4,allegra}!decwrl!johnsson johnsson@DECWRL.ARPA RHEA::JOHNSSON